Back to Meter GuideNeed Help or a Quote ?

A very high density (50 CT inputs) revenue-grade, multi-point electrical meter suitable for regulated markets. ‍

  • Accuracy: ANSI C12.20, Class 0.5
  • CT inputs: 50  
  • Configuration: 20 x 2-phase, 10 x 3-phase + 10 x 2-phase
  • Voltage: 120/208V or 120/240V Service voltages  — higher voltages with external PTs
  • CTs: 80mA Solid Core CTs or 5A:80mA CT convertors
  • Communications: − Ethernet (Native), V.90 Phone Modem
  • Pulse Inputs: 1

Features and Specifications

Device Configuration
  • 20 x 2-phase
  • 10 x 3-phase + 10 x 2-phase
Supported CTs
  • 80mA Solid Core CTs or 5A:80mA CT converters
Voltage Options
  • 120V, 60hz
  • 230V, 50hz
  • 240V, 60hz
  • 277V, 60hz
Communication Options
  • 10/100BaseT Full Duplex
  • DHCP Client or static IP address
  • Passive FTP port 21
  • NTP port 123
  • Modbus TCP/IP port 502
  • HTTP port 80
4-quadrant Meter Measurement (Total and Per Phase)
  • Active Power
  • Voltage
  • Pulse Count
Additional Features
  • One on-board pulse input (2 wire) compatible with dry form A and solid state form A contacts, collects data from other pulse-out meters (gas, water or electric)
  • On-board non-volatile flash memory is unaffected by power outages and holds up to 2 years of meter data (1 hour intervals for 20 years)
  • On-board Liquid Crystal Display
  • Multi-point economic efficiencies for retrofit or new construction
  • On-board real-time clock with battery back-up holds time up to 10 years
  • Remotely configurable and upgradable with Ethernet connectivity

Reporting and Communications

AMR via FTP data push over IP or (optional) MODEM
  • Plain text CSV file
  • Measurement Interval: 1 to 60 minutes
  • Reporting interval: once/day or every N minutes
Logged Measurements for AMR (interval and register)
  • Wh delivered
  • Vrms
  • Pulse counts
Ethernet Interface
  • 10/100BaseT Full Duplex
  • DHCP Client or static IP address
  • Passive FTP port 21
  • NTP port 123
  • Modbus TCP/IP port 502
  • BACnet IP port 47808
  • HTTP port 80
Other
  • BAS Integration via Modbus TCP/IP
  • On-board Web server and Liquid Crystal Display for local readings