Back to Meter GuideNeed Help or a Quote ?

A higher density (24 CT inputs) revenue-grade, multi-point electrical meter suitable for energy management in non-regulated markets. ‍

  • Accuracy: ANSI C12.20, Class 0.5
  • CT inputs: 24 
  • Configuration: 24 x 1-phase, 12 x 2-phase,  or 8 x 3-phase
  • Voltage: 120V CV, 90-300V Vref
  • CTs: 333mV split-core
  • Communications: Ethernet communications with native BACnet IP, Modbus TCP/IP, plus optional integrated V.90 telephone modem or Modbus RTU interface
  • Pulse Inputs: 2

Features and Specifications

Device Configuration
  • 24 single-phase meters
  • 12 two-phase or three-phase Delta meters
  • 8 three-phase Wye meters
Supported CTs
  • 333mV split-core CTS
Voltage Options
  • 120V, 60hz
  • 230V, 50hz
  • 240V, 60hz
  • 277V, 60hz
Communication Options
  • Ethernet (native)
  • Ethernet + V.90 Phone Modem
  • Ethernet + Modbus RTU
4-quadrant Meter Measurement (Total and Per Phase)
  • Active, Reactive & Apparent Power
  • Peak W and VA Demand
  • PF and phase angles
  • Irms, Vrms
Additional Features
  • Two on-board pulse inputs (2 wire) compatible with dry form A and solid state form A contacts, collect data from other pulse-out meters (gas, water or electric)
  • On-board non-volatile flash memory is unaffected by power outages and holds up to 2 years of meter data (1 hour intervals for 20 years)
  • On-board Liquid Crystal Display
  • On-board real-time clock with battery back-up holds time up to 10 years
  • Multi-point economic efficiencies for retrofit or new construction
  • Remotely configurable and upgradable with Ethernet connectivity

Reporting and Communications

AMR via FTP Data Push over IP or (optional) MODEM
  • Plain text CSV file
  • Measurement Interval: 1 to 60 minutes
  • Reporting interval: once/day or every N minutes
Logged Measurements for AMR (Interval and Register)
  • Wh delivered & received
  • VARh delivered & received
  • VAh
  • Peak W & VA Demand
  • Present W & VA Demand
  • Peak Current
  • Vrms
  • Pulse counts x 2 inputs
Ethernet Interface
  • 10/100BaseT Full Duplex
  • DHCP Client or static IP address
  • Passive FTP port 21
  • NTP port 123
  • Modbus TCP/IP port 502
  • BACnet IP port 47808
Other
  • BAS Integration bia BACnet IP, Modbus TCP/IP, or (optional) Modbus serial RTU
  • On-board Web server and Liquid Crystal Display for local readings

Support and Downloads

Meter Installation
Meter Configuration
Other
Close Let's Get Started Form Icon

How can we Help?

Thank you! Your submission has been received. Someone will be in touch shortly.

Oops! Something went wrong while submitting the form. Please try again.

Close Let's Quote Form Icon

Get a Quote

Thank you! Your submission has been received. Someone will be in touch shortly.

Oops! Something went wrong while submitting the form. Please try again.